Series TC

Products » Commercial Boilers » Series TC

The Series TC cast iron boiler can be used in either hot water or steam systems. The oil, gas or combination gas/oil-fired boiler is available in 15 sizes and is ideal for large commercial applications. The Series TC boiler is designed with forced draft firing to provide the highest possible efficiencies. The boiler’s gross output ratings range from 900 to 4,629 MBH.

Series TC boilers are constructed of rugged, cast-iron, wet-base sections with cast-in heat extraction pins that assure durability and top performance. Hi-temperature, flexible, graphite port connectors, and short, individual draw rods simplify installation. Front and rear flame observation ports aid burner setup.

All Series TC boilers are available with a standard, built-in cast iron flue collector with integral damper and a burner mounting plate with insulation block. Steel angle floor rails and ceramic fiber rope seal between sections are also standard. Series TC boilers feature 80 psi working pressure sections. A 30 psi ASME safety relief valve is standard on water boilers. Steam boilers include a 15 psi ASME side outlet safety valve and steam gauge. All Series TC boilers are equipped with an insulated enameled steel jacket.

Peerless Series TC boilers are available with your choice of Beckett, Carlin, Power Flame or Webster burners.

PureFlow Technology

Series TC hot water, cast iron boilers are now equipped with the new PureFlow technology. The PureFlow system assures a stable return temperature and is the simplest, most effective method to reduce or eliminate stress failures in cast iron boilers. Installation of the PureFlow system is simple and requires no additional controls, pumps or piping. Each PureFlow system is completely self-adjusting and sized for a specific TC boiler model.

read more

Type: Commercial
Construction: Cast Iron
Fuel: Oil, Gas, Gas/Oil-Fired
Input: 1,154 to 5,862 MBH
Output: 900 to 4,629 MBH
Venting: Forced Draft
Trim: Water or Steam
Combustion: Power Burner

  • Power Burner — Oil, Gas, Gas/Oil
  • Steam or Hot Water Boilers
  • Rugged, Cast-Iron Construction
  • Forced Draft Venting
  • Wet-Base Sections
  • Cast-in Heat Extraction Pins
  • Integral Cast Iron Flue Collector
  • Hi-Temperature, Flexible, Graphite Port Connectors

Don't see the information you need? See the "Related Documents" tab for product resource downloads.

Series TC Water Content Water Working Weight, lb
Model Number Oil Input2 Gas Input3, MBH Net I=B=R Ratings1 Oil Gas Steam, Gal Water, Gal
GPH MBH Steam, sqft Steam3, MBH Water2, MBH Combustion Efficiency5, % Thermal Efficiency5, % Combustion Efficiency5, % Thermal Efficiency5, %
TC-04 8.0 1120 1154 2813 675 783 83.5 80.4 81.0 78.0 123.4 103.8 4215
TC-05 10.4 1456 1491 3646 875 1014 83.5 80.7 81.0 78.2 150.3 125.8 5038
TC-06 12.6 1764 1827 4538 1089 1246 83.5 80.8 81.0 78.4 177.2 147.8 5861
TC-07 15.0 2100 2163 5458 1310 1477 83.5 81.0 81.0 78.5 204.1 169.8 6684
TC-08 17.4 2436 2499 6358 1526 1709 83.5 81.1 81.0 78.6 231.0 191.8 7507
TC-09 19.6 2744 2836 7221 1733 1941 83.5 81.1 81.0 78.7 257.9 213.8 8331
TC-10 22.0 3080 3172 8079 1939 2172 83.5 81.2 81.0 78.8 284.8 235.8 9169
TC-11 24.5 3430 3508 8942 2146 2403 83.5 81.2 81.0 78.8 311.7 257.8 9992
TC-12 26.5 3710 3844 9804 2353 2636 83.5 81.3 81.0 78.8 338.6 279.8 10,815
TC-13 29.0 4060 4180 10,667 2560 2867 83.5 81.3 81.0 78.9 365.5 301.8 11,649
TC-14 31.5 4410 4517 11,525 2766 3098 83.5 81.3 81.0 78.9 392.4 323.8 12,467
TC-15 33.5 4690 4853 12,392 2974 330 83.5 81.4 81.0 78.9 419.3 345.8 13,511
TC-16 36.0 5040 5189 13,250 3180 3562 83.5 81.4 81.0 78.9 446.2 367.8 14,375
TC-17 38.5 5390 5525 14,113 3387 3793 83.5 81.4 81.0 79.0 473.1 389.8 15,239
TC-18 40.5 5670 5862 14,975 3594 4025 83.5 81.4 81.0 79.0 500.0 411.8 16,103

1 Net I=B=R Water Ratings are based on allowance of 1.15. Net I=B=R Ratings for steam boilers are based on piping and pick-up factor as follows: 4 and 5 section = 1.333, 6-section = 1.305, 8 section and larger = 1.288.

2 Light oil having a heat content of 140,000 BTU/Gal.

3 Gas having a heat content of 1,000 BTU/Cu. Ft., 0.60 specific gravity.

Don't see the information you need? See the "Related Documents" tab for product resource downloads.

Series TC Boiler Dimensions

Boiler Model Number Overall Length - "A" 2 Optional Packaged Base Dimension "K" Furnace Length "B" Boiler Length "C" Steam Uptake Locations 3 Draft Loss Ins. W.C. Firebox Press. Ins. W.C.* Dia. Vent Conn. "G" Height Vent Conn. "H"1
Carlin Beckett Power Flame Webster "D" "E" "F"
TC-04 62 1/4" 64" 71 5/8" 66 3/8" 91 3/16" 23 5/16" 33" 12 1/2" - - .24 .34 10" 57 5/8"
TC-05 70 1/4" 72" 83 1/8" 74 3/8" 104 1/4" 31 5/16" 41" 20 1/2" - - .25 .35 10" 57 5/8"
TC-06 80 1/8" 80 1/4" 91 1/8" 82 3/8" 112 5/16" 39 5/16" 49" 12 1/2" 16" - .26 .36 10" 57 5/8"
TC-07 88 1/8" 88 5/8" 99 1/8" 90 3/8" 120 3/8" 47 5/16" 57" 12 1/2" 24" - .27 .37 12" 56 5/8"
TC-08 96 1/8" 96 3/4" 107 1/8" 98 3/8" 128 7/16" 55 5/16" 65" 12 1/2" 32" - .28 .38 12" 56 5/8"
TC-09 108 7/8" 104 3/4" 115 1/8" 110 3/8" 136 1/2" 63 5/16" 73" 12 1/2" 40" - .29 .39 14" 55 5/8"
TC-10 116 7/8" 116 3/8" 128" 118 3/8" 144 9/16" 71 5/16" 81" 20 1/2" 40" - .30 .40 14" 55 5/8"
TC-11 125 1/8" 124 3/8" 137 1/8" 126 3/8" 157 5/8" 79 5/16" 89" 20 1/2" 24" 24" .31 .41 14" 55 5/8"
TC-12 133 1/8" 132 1/2" 145 1/8" 134 3/8" 165 1 1/16" 87 5/16" 97" 20 1/2" 24" 32" .33 .43 14" 55 5/8"
TC-13 141 1/8" - 153 1/8" 142 3/8" 173 3/4" 95 5/16" 105" 20 1/2" 32" 32" .34 .44 14" 55 5/8"
TC-14 149 1/8" - 161 1/8" 150 3/8" 181 1 3/16" 103 5/16" 113" 20 1/2" 32" 40" .35 .45 16" 54 5/8"
TC-15 - - 169 1/8" 158 3/8" 189 7/8" 111 5/16" 121" 20 1/2" 40" 40" .36 .46 16" 54 5/8"
TC-16 - - 177 1/8" 166 3/8" 197 15/16" 119 5/16" 129" 20 1/2" 48" 40" .37 .47 16" 54 5/8"
TC-17 - - 191 1/8" 183 7/8" 211" 127 5/16" 137" 20 1/2" 48" 48" .38 .48 18" 54 5/8"
TC-18 - - 199 1/8" 191 7/8" 219 1/16" 135 5/16" 145" 20 1/2" 56" 48" .39 .49 18" 54 5/8"
  1. When unit is assembled or packaged, add 6" to heights for 4 - 14 sec., 8" to heights for 15 - 18 sect.
  2. Add 2-3/4" to sections 17 and 18 for flue outlet adapter. *Based on 0.10 ins. W.C. pressure at boiler outlet. If vent sizing results in a back pressure greater than 0.10 ins. W.C., consult Peerless Heater Company.
  3. These measurements are approximate.

Don't see the information you need? See the "Related Documents" tab for product resource downloads.